Description
A burner decides whether a boiler meets its emission limit and how well it follows load. The AIX-BRN series is a proportional (modulating) packaged burner with a matched fan, servo-driven air damper, and a flame scanner that watches the whole firing range rather than only high fire.
Firing modes and fuel flexibility
- Gas: natural gas, LPG, biogas, LNG vapour.
- Oil: light diesel, heavy fuel oil with preheating and atomising air.
- Dual fuel: automatic changeover with separate proven trains.
Technical specification
| Parameter | Range |
|---|---|
| Thermal output | 0.5 – 20 MW |
| Turndown | 5:1 standard, 8:1 on request |
| NOx (gas) | ≤ 30 mg/m³ @ 3.5 % O₂ (FGR where required) |
| Control | Proportional / PID, 4–20 mA or Modbus |
| Safety | BMS to EN 746-2, UV/IR flame scanner, double gas train |
| Mounting | Flange to boiler front plate, hinge for swing-out service |
Retrofit and new-build use
Most enquiries are retrofits: an existing boiler with an old on/off burner cannot hold a 30 mg/m³ limit or a stable low-fire. In those cases we match the burner to the furnace volume and the return-air connection, then verify the flame shape on site. For new boilers the burner is selected together with the furnace so the flame does not impinge on the tube plate.
What is supplied
Burner body, blower, gas train or oil pump set, servo actuators, flame scanner, local control panel and the interface cable schedule. Commissioning includes combustion analysis at low, mid and high fire, with a printed report for the permit file.
FAQ
Will a low-NOx burner fit my existing boiler? Usually yes, if the furnace volume and front-plate opening suit the flame. We check both from your drawing before quoting.
Do you supply FGR? Yes — flue gas recirculation is added when 30 mg/m³ cannot be reached with air staging alone.