Description
Most boiler failures that are not mechanical start with water. Scale insulates the tube, overheating follows, and the repair costs more than a decade of treatment. This package covers the four stages that matter: softening, demineralisation or RO, deaeration, and chemical dosing.
Stages
- Softener: strong-acid cation resin, automatic regeneration by hardness or volume.
- RO: removes 95–99 % of dissolved solids where TDS or alkalinity is high.
- Deaerator: removes oxygen and CO₂ thermally, typically to below 0.02 mg/L O₂.
- Dosing: oxygen scavenger, antiscalant, and pH / phosphate control with metering pumps.
Technical specification
| Parameter | Range |
|---|---|
| Softener flow | 1 – 50 m³/h |
| Outlet hardness | < 0.03 mmol/L |
| RO recovery | 60 – 75 % |
| RO outlet conductivity | < 10 µS/cm |
| Deaerator outlet O₂ | < 0.02 mg/L |
| Control | PLC with conductivity and hardness alarms |
What to specify
Send the raw water analysis (hardness, alkalinity, TDS, silica, chloride), the make-up flow and the boiler pressure. Those numbers set the resin volume, the RO membrane array and the dosing rates. A treatment plant sized on flow alone will either be oversized or will fail on silica.
Maintenance
Salt for regeneration, resin inspection annually, membrane cleaning every 6–12 months depending on fouling, and daily logging of hardness and conductivity. The log is the cheapest early warning a plant has.
FAQ
Do I need RO if I already soften? Only if TDS, alkalinity or silica exceed the boiler limits; softening alone does not remove dissolved solids.
Can the package be containerised? Yes, in a 10 or 20 ft container for remote sites.